Communication objectsCommunication objectsProduct manual 2CKA001473B9679 │35712.1.70 RTC - Fan speed level x (cooling)Name Object function Data typeRTC: Fan speed level x (cooling) Output 1.001 SwitchingThese, up to five communication objects send the current fan speed level of the second fan coilactuator (cooling) via 1-bit switching commands to the actuator.If a fain coil regulator is set for both operating modes of heating and cooling and an owngenerating device is set for both operating modes, this communication object then operatesjointly with fan coil regulator cooling.12.1.71 RTC - Current HVAC operating modeName Object function Data typeRTC: Current HVAC operatingmode Output 20.102 HVAC modeThe RTC uses this communication object to send the operating mode that belongs to thecurrently set setpoint temperature.RTC operating mode Current HVAC operating modeError Building protectionComfort override operating mode ComfortStandby override operating mode StandbyEconomy: Override operating mode EconomyBuilding protection override operating mode Building protectionCondensate water alarm Building protectionDew point alarm Building protectionWindow open Building protectionControl OFF Building protectionPresence ComfortComfort ComfortStandby StandbyEconomy EconomyBuilding protection Building protectionTable 8: Operating mode