Communication objectsCommunication objectsProduct manual 2CKA001473B9679 │35012.1.47 RTC - Confirm setpointName Object function Data typeRTC: Confirm set value (master) Output9.001 Temperature value9.002 Differential temperature value6.010 Counter valueRTC: Confirm set value (slave) Input9.001 Temperature value9.002 Differential temperature value6.010 Counter valueThe communication object is used to transmit the setpoint confirmation of the master device to aslave device. The format can be an absolute or relative temperature value or a counter valuewhich is multiplied with an adjustable step size (standard value 0.5 K). This value the slavedevice adopts as starting point for a further setpoint adjustment.NoticeWhen the master/slave operation is activated, the object "RTC: Confirm setpoint(master)" of the master device for synchronisation must be connected withobject "RTC: Confirm setpoint (slave)" of the slave device.12.1.48 RTC - Heating/cooling requestName Object function Data typeRTC: Heating/cooling request(Master) Input 1.100 Heating / CoolingRTC: Heating/cooling request(Slave) Output 1.100 Heating / CoolingThe communication object is used to transmit the heating/cooling switchover request of thebutton operation of a slave device to the master device. The confirmation is made via object"Heating/cooling switchover".NoticeWhen the master/slave operation is activated, the object "RTC: Heating/coolingrequest (master)" of the master device for synchronisation must be connectedwith object "RTC: Heating/cooling request (slave)" of the slave device.