Description of application and parametersApplication "RTC"Product manual 2CKA001473B9679 │11611.4.64 Settings of basic loadNoteOnly available when the "Device function" parameter is set on either "Singledevice" or "Master device" and the control function parameter is set on either"Heating with additional stage", "Cooling with additional stage", "Heating andcooling" or "Heating and cooling with additional stages".11.4.65 Settings of basic load — Minimum control value for basic load > 0Options: Always activeActivate via objectThe function finds application when in the desired area, e.g. with floor heating, the floor is tohave a basic warmth. The size of the minimum control value specifies the volume of heatingmedium that flows through the controlled area, even when the calculation of the control value ofthe controller would indicate a lower value.– Always active: Here it is possible to define whether this basic load will be permanently activeor whether it will be switched via the "Basic load" object.– Activate via object: When this parameter is selected, the basic load function, which meansthe minimum control value with a value higher than zero, can be activated (1) or deactivated(2). If it is activated, then the heating medium will always be fed through the system with atleast the minimum control value. If it is deactivated, the control value can be reduced to zerowith the controller.11.4.66 Basic load settings — Basic load active when controller is offOptions: NoYes– This parameter switches the basic load active when the controller is off.NoteThis parameter is only available when "Control value type" parameter is seteither on "PI continuous, 0 – 100%", "PI PWM, On/Off“ or "Fan coil".