Description of application and parametersApplication "Function block x"Product manual 2CKA001473B9679 │22911.7.7.5 Value for position down (%)Options: Setting option from 0 to 100 (%)The parameter is used to set the position to which a linked blind is to be lowered. Theassociated 1-byte communication object "Sx: position" must hereby be connected with a 1-byteposition object of the blind actuator.Percentage values can be set in steps of 1%. Meaning of the percentage values:■ 0% = blind completely raised.■ 100% = blind completely lowered.NoteThe parameter can only be set if the "Blind/roller blind switchover function"parameter is set on "Blind" and the "Object type" parameter is set on "1-byte 0-100%.11.7.7.6 Value for position up (%)Options: Setting option from 0 to 100 (%)The parameter is used to set the position to which a linked blind is to be raised. The associated1-byte communication object "Sx: position" must hereby be connected with a 1-byte positionobject of the blind actuator.Percentage values can be set in steps of 1%. Meaning of the percentage values:■ 0% = blind completely raised.■ 100% = blind completely lowered.NoteThe parameter can only be set if the "Blind/roller blind switchover function"parameter is set on "Blind" and the "Object type" parameter is set on "1-byte 0-100%.