Description of application and parameters"Relative humidity" applicationProduct manual 2CKA001473B9679 │20311.6.57 Dew point alarm — Dew point alarmOptions: InactiveActiveIf an alarm is sent when the parameterised dew point is exceeded, the parameter must be set to"active". A corresponding communication object is displayed in ETS in parallel.11.6.58 Dew point alarm — Dew point alarm advanceOptions: 01°C2°C3°C4°C5°CIf the alarm is triggered before the dew point is reached, the advance can be set using thisparameter. In this way, for example, a fan can be activated before the dew point alarm isreached so that the alarm case is delayed or does not even occur.11.6.59 Dew point alarm — Dew point alarm hysteresis (symmetrical)Options: 01°C2°C3°C4°C5°CThe basic set value has a hysteresis. If the parameterised hysteresis value isexceeded/undershot, the corresponding value is sent.11.6.60 Dew point alarm — Send dew point alarm at status changeOptions: InactiveActiveIf a changed value/status is present, it can be activated and sent to the KNX bus via thecorresponding communication object.