Description of application and parametersApplication "General functions"Product manual 2CKA001473B9679 │30411.9.4.7 Object type outputOptions: 1 bit1 byte■ 1 bit:– Object "GFx: output“ consists of a 1-bit value (0/1).■ 1 byte:– Object "GFx: output“ consists of a 1-byte value (0 - 255).Each logic function has an output object. The result determined from the inputs is sent on thebus via the output object.The parameter is used to specify the bit size for the output object.11.9.4.8 Send output objectOptions: With each input telegramWith a change of the output object■ With each input telegram:– When a telegram is received via the input object, the communication object alwayssends the value of the output object on the bus. This also happens if the value of theoutput object has not changed.■ With a change of the output object:– The communication object only sends a telegram when the value of the output objecthas changed.The parameter is used to specify whether a telegram is sent via communication object "GFx:output" at each receipt of a telegram or only at a change of the output object.