Description of application and parametersApplication "RTC"Product manual 2CKA001473B9679 │12311.4.9 Setpoint settings — Increase for standby cooling (°C)Options: Setting option between 0 - 15Specifies the temperature in cooling mode when nobody is present. On devices with a display,this mode is indicated by the standby icon.NoteThis parameter is only available when the "Control function" parameter is set on"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating andcooling with additional stages".11.4.10 Setpoint settings — Increase for ECO cooling (°C)Options: Setting option between 0 - 15Specifies the temperature in cooling mode when nobody is present. On devices with a display,this mode is indicated by the eco icon.NoteThis parameter is only available when the "Control function" parameter is set on"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating andcooling with additional stages".11.4.11 Setpoint settings — Set-point temperature for heat protection (°C)Options: Setting option between 27 - 45Function for protecting the building against heat. On devices with a display, this mode isindicated by the heat protection icon. Manual operation is blocked.NoteThis parameter is only available when the "Control function" parameter is set on"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating andcooling with additional stages".