Chapter 7 Servo ParametersRevision June 2010 7-59Display Format: DecimalSettings:This parameter is used to set magnitude of the resonance suppression that is setby parameter P2-43. If P2-44 is set to 0, the parameters P2-43 and P2-44 are bothdisabled.P2 - 45 NCF3 Notch Filter 3 (Resonance Suppression) Address: 025AH, 025BHDefault: 1000 Related Section:Applicable Control Mode: ALL Section 6.3.7Unit: HzRange: 50 ~ 2000Data Size: 16-bitDisplay Format: DecimalSettings:This parameter is used to set third resonance frequency of mechanical system. Itcan be used to suppress the resonance of mechanical system and reduce thevibration of mechanical system.If P2-45 is set to 0, this parameter is disabled.P2 - 46 DPH3 Notch Filter Attenuation Rate 3(Resonance Suppression) Address: 025CH, 025DHDefault: 0 Related Section:Applicable Control Mode: ALL Section 6.3.7Unit: dBRange: 0 ~ 32Data Size: 16-bitDisplay Format: DecimalSettings:This parameter is used to set magnitude of the resonance suppression that is setby parameter P2-45. If P2-46 is set to 0, the parameters P2-45 and P2-46 are bothdisabled.P2 - 47 ANCF Auto Resonance Suppression ModeSelection Address: 025EH, 025FHDefault: 1 Related Section: N/AApplicable Control Mode: ALLUnit: N/ARange: 0 ~ 2Data Size: 16-bitDisplay Format: Decimal