106 Eaton® Power Xpert® 9395P-1200 Installation and Operation Manual 164000500—Rev 1155..44 IInnssttaalllliinngg aann OOppttiioonnaall RReellaayy IInntteerrffaaccee MMoodduullee IIIITo install RIM II wiring:1. Verify the UPS system is turned off and all power sources are removed. SeeChapter 7 UPS Operating Instructions for shutdown instructions.2. Perform the procedure listed in paragraph5.1 Installing an Optional Powerware Hot Sync CAN Bridge Card.NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within thewall. Do not use hollow wall anchors.3. Securely mount the RIM II at the desired location. See Figure 60 for mounting hole locations.NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installedbetween the device and the UPS cabinet.4. Remove the UPS cabinet top interface conduit landing plates to drill or punch conduit holes (see Figure 32).5. Reinstall the conduit landing plate.6. Install conduit between the UPS and RIM II. See Figure 60 for RIM II knockout hole location.7. Install wiring between the UPS and RIM II. See Figure 49 and Table 29 for the Powerware Hot Sync CANBridge Card terminal location and wiring information, and Figure 54, Figure 55, and Table 33 for the RIM IIterminal location and wiring information.NOTE 120 Vac for the RIM II should be supplied from the critical bus by facility planners or thecustomer.8. Install 120 Vac power wiring from the critical bus to the RIM II. See Figure 54, Figure 55, and Table 33 forthe terminal location and wiring information.9. Close the front door and secure the latch.10. Restart the UPS. See Chapter 7 UPS Operating Instructions for startup instructions.NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by anauthorized Eaton Customer Service Engineer. Contact an Eaton service representativeto schedule a date.11. Contact an Eaton service representative for verification and testing of the RIM II and its connections priorto making connections with J1 through J4 (see Table 34 and Figure 56).You can order interface cables separately for connecting to the 15–Pin D–Sub Connectors.Installing Options and Accessories