44 Eaton® Power Xpert® 9395P-1200 Installation and Operation Manual 164000500—Rev 11To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratingsfrom Table 23 in accordance with the NEC, ANSI/NFPA 70.ATTENTION!Pour réduire le risque d’incendie, ne brancher qu’à un circuit avec le courant nominal maximal du disjoncteurd’entrée indique dans le tableau (Table 23) conformement à la norme ANSI/ NFPA 70 du NEC.Table 24. Recommended Bypass, Output, and MOB Circuit Breaker Ratings (100% and 80% Load Rating)UPS ModelInput Rating% 480V 415V 400V 380VEaton 9395P-1200/1200 100 1600A N/A N/A N/A80 2000A N/A N/A N/AEaton 9395P-1200/1100 100 1600A 1600A 1600A 2000A80 2000A 2000A 2000A 2500AEaton 9395P-1200/1000 100 1600A 1600A 1600A 1600A80 1600A 2000A 2000A 2000AEaton 9395P-1200/900 100 1200A 1600A 1600A 1600A80 1600A 2000A 2000A 2000AEaton 9395P-1200/825 100 1000A 1200A 1200A 1600A80 1600A 1600A 1600A 1600AEaton 9395P-1200/750 100 1000A 1200A 1200A 1200A80 1200A 1600A 1600A 1600AEaton 9395P-1200/675 100 1000A 1000A 1000A 1200A80 1200A 1200A 1600A 1600ANOTE Bypass conduit data is not applicable to IOM configurations.There is no manual DC disconnect device within the UPS.A battery disconnect switch is required for battery systems and may also be required by NEC or local codes.The battery disconnect switch should be installed between the battery and the UPS.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current iscomputed at 2 volts per cell.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% ofnominal DC voltage at rated battery current.External DC input overcurrent protection and disconnect switch is to be provided by the customer. Table 26and Table 26 list the maximum ratings for continuous–duty rated circuit breakers satisfying the criteria for both.Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longerdischarge times a larger disconnect may be required.UPS Installation Plan and Unpacking