Eaton® Power Xpert® 9395P-1200 Installation and Operation Manual 164000500—Rev 11 39Table 17. Supplied Intercabinet Wiring Terminal Hardware KitPart Size Quantity Terminals Used On Eaton PartNumberFlat Washer M8 36 UPM AC Input, UPM Battery Input,UPM AC Output 180500036-080Conical Washer M8 36 UPM AC Input, UPM Battery Input,UPM AC Output 180500037-080Nut M8 36 UPM AC Input, UPM Battery Input,UPM AC Output 180200001-05Terminals E1 through E11 are 2-hole busbar mountings for standard NEMA 2-hole barrel lugs. The power wiringconnections for this equipment are rated at 90°C. See Table 18 for power cable terminations, Table 19 forsupplied terminal hardware, and Table 20 for recommended installation parts and tools not supplied by Eaton.Figure 33 through Figure 36 show the location of the power cable terminals inside the UPS.Table 18. UPS External Power Cable Terminations for Three/Four UPM ModelsTerminal Function Terminal Function Bus Landings (usingboth sides of bus)Tightening TorqueNm (lb ft) Bolt SizeAC Input to UPS RectifierE1 Phase A 8 – 2 bolt mounting 76 (56) M12E2 Phase B 8 – 2 bolt mounting 76 (56) M12E3 Phase C 8 – 2 bolt mounting 76 (56) M12AC Input to BypassE6 Phase A 6 – 2 bolt mounting 76 (56) M12E7 Phase B 6 – 2 bolt mounting 76 (56) M12E8 Phase C 6 – 2 bolt mounting 76 (56) M12AC Output to Critical LoadE9 Phase A 8 – 2 bolt mounting 76 (56) M12E10 Phase B 8 – 2 bolt mounting 76 (56) M12E11 Phase C 8 – 2 bolt mounting 76 (56) M12DC Input from Battery orBattery Disconnect to UPS– Common BatteryE4 Battery (+) 16 – 2 bolt mounting 76 (56) M12E5 Battery (-) 16 – 2 bolt mounting 76 (56) M12DC Input from Battery orBattery Disconnect to UPS– Separate Battery (UPM 1)E4 Battery (+) 4 – 2 bolt mounting 76 (56) M12E5 Battery (-) 4 – 2 bolt mounting 76 (56) M12DC Input from Battery orBattery Disconnect to UPS– Separate Battery (UPM 2)E4 Battery (+) 4 – 2 bolt mounting 76 (56) M12E5 Battery (-) 4 – 2 bolt mounting 76 (56) M12DC Input from Battery orBattery Disconnect to UPS– Separate Battery (UPM 3)E4 Battery (+) 4 – 2 bolt mounting 76 (56) M12E5 Battery (-) 4 – 2 bolt mounting 76 (56) M12UPS Installation Plan and Unpacking