Eaton® Power Xpert® 9395P-1200 Installation and Operation Manual 164000500—Rev 11 17• The system must be installed in a temperature and humidity controlled indoor area free of conductivecontaminants.• The cabinet can be installed in line-up-and-match or standalone configurations.Failure to follow guidelines may void your warranty.The UPS equipment operating environment must meet the weight requirements shown in Table 2 and the sizerequirements shown in Figure 3 through Figure 14. Dimensions are in millimeters (inches).Table 2 includes the weights of the heaviest cabinet configuration. Actual weights may be less due to installedconfiguration. Weights are in kilograms (pounds).Table 2. UPS Cabinet Maximum WeightsModelSectionMaximum Weight kg (lb)Shipping InstalledPower Xpert 9395P-1200/1200Power Xpert 9395P-1200/1100Power Xpert 9395P-1200/1000ISBM (CSS) 952 (2099) 908 (2002)3XUPM 1667 (3675) 1620 (3571)FI-UPM 500 (1102) 475 (1047)Power Xpert 9395P-1200/900Power Xpert 9395P-1200/825Power Xpert 9395P-1200/750Power Xpert 9395P-1200/675ISBM (CSS) 952 (2099) 908 (2002)3XUPM 1667 (3675) 1620 (3571)NOTE CSS = Continuous Static SwitchThe UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the frontof the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper aircirculation. The clearances required around the UPS cabinet are shown in Table 3. Dimensions are inmillimeters (inches).Table 3. UPS Cabinet ClearancesFrom Top of Cabinet 457.2 mm (18") minimum clearance for ventilationFrom Front of Cabinet 914.4 mm (36") working spaceFrom Back of Cabinet None RequiredFrom Right Side of Cabinet None RequiredFrom Left Side of Cabinet None RequiredThe basic environmental requirements for operation of the UPS are:• Ambient Temperature Range:– ALL RATINGS EXCEPT 1200 kW, 900 kW: 0–40º C (32–104º F)– For 1200 kW, 900 kW: 0–35°C (32–95°F) at elevations up to 1000 m without derating.• Recommended Operating Range: 20–25º C (68–77º F)• Maximum Relative Humidity: 95%, non-condensingUPS Installation Plan and Unpacking