36 Eaton® Power Xpert® 9395P-1200 Installation and Operation Manual 164000500—Rev 11Table 14. 380V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – CommonBatteryBasic Unit RatingUnits Rating 50/60 HzkVAkW6756757507508258259009001000100011001100Input and Output Voltage Volts 380/380 380/380 380/380 380/380 380/380 380/380AC Input to UPS Rectifier (0.98 Minimum pF)Full load current plus battery recharge current(3) Phases, (1) Ground AAmps 1200 1363 1500 1600 1818 2000Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)500(5)500(6)500(6)500(6)500(8)500(8)AC Input to UPS Bypass (Five Wire)Full Load Current(3) Phases, (1) Neutral, (1) Ground BAmps 1026 1139 1253 1367 1519 1671Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)500(5)500(5)500(5)500(6)500(6)500(8)DC Input from Battery Disconnect(1) Positive, (1) NegativeCAmps 1480 1645 1809 1974 2193 2412Minimum Conductor SizeNumber per PoleAWG or kcmil(each)500(6)500(8)500(8)500(8)500(9)500(12)AC Output to Critical Load (Five Wire)Full Load Current(3) Phases, (1) Neutral, (1) Ground DAmps 1026 1139 1253 1367 1519 1671Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)500(5)500(5)500(5)500(6)500(6)500(8)NOTE Callout letters A, B, C, and D map to Figure 66.NOTE Bypass wiring data is not applicable to IOM configurations.Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above foroptimum system performance and battery run time.Battery Cable Routing RequirementsConduit applications:* Each conduit must have a Positive, Negative, and Ground conductor.* There must be an equal number of positive and negative conductors in a single conduit. Only one ground conductor is required ineach conduit.Raceway applications:* Positive and negative battery cables must be run side by side in the raceway in an alternating pattern (+ - + - + - + -).* There must be a ground cable running in the raceway with the battery cables.NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it mayinterrupt the UPS input neutral during its transition between sources. For the 9395 UPS:The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS tooperate properly, however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt thereturn current path and cause a loss of all phase-to-neutral loads.If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during thetransition.UPS Installation Plan and Unpacking