166 Eaton® Power Xpert® 9395P-1200 Installation and Operation Manual 164000500—Rev 11To obtain any system information, follow the on screen prompts to get to the proper screen. The operatorcannot inadvertently cause a system dump or disconnect unless they override a warning pop-up. Value orinformation screens DO NOT affect system operation.77..44..22 UUssiinngg tthhee RReemmoottee EEmmeerrggeennccyy PPoowweerr--ooffff SSwwiittcchhA UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use thisswitch to control the UPS output. The REPO switch de–energizes the critical load and powers down the UPSimmediately, without asking for verification.The UPS, including Bypass, remains off until restarted.All power to the critical load is lost when the REPO switch is activated in the following step. You should usethis feature only when you want to de–energize the critical load.ATTENTION!L’alimentation de la charge critique est complètement coupée lorsque le circuit d’arrêt d’urgence à distance estdéclenché à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension.NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to theoperating instructions provided with the switch.To use the REPO switch:1. Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (seeFigure 119).The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, andthe power module is turned off immediately, without asking for verification.Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified andcleared.ATTENTION!Ne pas tenter de redémarrer le système après le déclenchement du circuit d’arrêt d’urgence à distance avantd’avoir déterminé la raison du déclenchement.2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotateclockwise until the red pushbutton releases (see Figure 119). To remove the key, rotate the key back tothe vertical position.3. Restart the UPS by following the procedure in paragraph 7.4.1 Starting the UPS in Online Mode.Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.UPS Operating Instructions