4 Commissioning4.3 Cyclic dataDX-NET-SWD 06/13 MN04012009Z-EN www.eaton.com 294.3.2 Profile 1 (8 bit): Inputs (status)Input bytes 0 and 1 (Short) are mapped as follows on SmartWire-DT.Table 6: Profile 10: Input bytes 0 and 1Byte BIT Designation Meaning0 0, 1 – Not used2, 3 A1, A2 1-0-A- switch on DX-NET-SWD:00: not defined10: Position A: Automatic (commands via SmartWire-DT/control signal terminal)01: Position 0: variable frequency drive stop11: Position 1: variable frequency drive operation4 DIAG 0: no diagnostic alarm1: Diagnostic alarm present5 – Not used6 PRSNT 0: Device not present1: Device present7 SUBST 0: Configured module present1: Universal module M22-SWD-NOP(C) present1 0 ERR Error present0: no error1: Error1 WARN Warning present:0: no warning1: Warning2 RDY Ready, switched on:0: not switched on1: switched on3 f = f-ref Running at setpoint:0: Ref. frequency not reached1: Ref. frequency reached4 f-Level Actual speed is greater than the signaling threshold0: Actual speed is less than or equal to the signalingthreshold1: Actual speed is greater than the signalingthreshold5 Q 1 Device Info Q16 Q2 Device Info Q27 Q3 Device Info Q3