4 Commissioning4.4 Acyclic data36 DX-NET-SWD 06/13 MN04012009Z-EN www.eaton.com4.4.3 List of parametersTable 10: List of parametersPNU indexPNU subindex AccessrightDatatypeMeaning DisplaynumberValue Range Description1 0 ro N2 Frequency reference value/Motorshaft speedP00-03 -16384 - 16384 4000 hex = 100 %, 100 % = P-015 1 rw N2 Preset speed 1 P-20 -16384 - 16383 4000 hex = 100 %, 100 % = P-015 2 rw N2 Preset speed 2 P-21 -16384 - 16383 4000 hex = 100 %, 100 % = P-015 3 rw N2 Preset speed 3 P-22 -16384 - 16383 4000 hex = 100 %, 100 % = P-015 4 rw N2 Preset speed 4 P-23 -16384 - 16383 4000 hex = 100 %, 100 % = P-0120 1 rw U16 Maximum speed limit P-01 0 - 5xP-09 3000 ≙ 50 Hz20 0 rw U16 Minimum speed limit P-02 0 - P-01 3000 ≙ 50 Hz21 0 rw U16 Skip frequency band width P-26 0 - P-01 3000 ≙ 50 Hz22 0 rw U16 Skip frequency / center point P-27 0 - P-01 3000 ≙ 50 Hz23 0 rw U16 Adaptation voltageU/f characteristic curveP-28 0 - P-07 Details in Volt24 0 rw U16 Adaptation frequency U/fcharacteristic curveP-29 0 - P-09 Details in Hz27 0 rw U16 Boost P-11 FS1 0 - 200FS2 0 - 150FS3 0 - 100100 ≙ 10 %28 0 rw Boost frequency P-32 Only available with alternatingcurrent motor types29 0 rw Boost time P-33 Only available with alternatingcurrent motor types111 0 rw T2 Acceleration ramp time P-03 0 - 6000 - 6000300 ≙ 3.00 s114 0 rw T2 Deceleration ramp time P-04 0 - 6000 - 6000300 ≙ 3.00 s116 0 rw T2 Second deceleration ramp time P-24 0 - 2500 250 ≙ 2.50 s202 0 ro Octet[3] Variable frequency drive part no. P00-20 String: e.g., “DC1“203 0 rw UInt16 HW version Hardware version of thevariable frequency drive203 1 rw UInt16 HW version net Hardware version of the SWDInterfaces206 1 ro U16 Software version, control section P00-18 103 = 1.03206 0 ro S16 Software version power section P00-18 103 = 1.03209 0 ro Octet[11] Variable frequency drive serialnumberP00-19 11 byte ASCII code210 0 rw U16 Rated motor current P-08 0 - depending ondevicewith one decimal pointe.g.14 ≙ 1.4 A211 0 rw U16 Nominal motor voltage P-07 0 - 500 Details in Volt