4 Commissioning4.4 Acyclic data54 DX-NET-SWD 06/13 MN04012009Z-EN www.eaton.comSmartWire-DT read response(+) – Without dataAs soon as the DC1 variable frequency drive has completed the response fora write job, it will send a SmartWire-DT read response(+) – without data.SmartWire-DT read response(+) – With data (all PNUs)As soon as the DC1 variable frequency drive has completed the response fora read job for the range PNU 0 – PNU 999 (without PNU 202), it will send aSmartWire-DT read response(+) – with data.SmartWire-DT read response(+) – with data (PNU 202)As soon as the DC1 variable frequency drive has completed the response fora read job of the PNU 202, it will send a SmartWire-DT read response(+) –with data.Byte Designation Description0 Request Reference Request identification: Is echoed1 Response-ID Response ID: 02 hex : Write job (+)2 DO-ID Drive-Object-ID: Is echoed3 No. of Parameters Number of parameters: 01 hexByte Designation Description0 Request Reference Request identification: Is echoed1 Response-ID Response ID: 01 hex : Read job (+)2 DO-ID Drive-Object-ID: Is echoed3 No. of Parameters Number of parameters: 01 hex4 Format Format: 01 hex – 7C hex (i. e. 01dez – 124 dez )5 No. of Values Number of values: 01 hex : value6 - 9 Value Value: Specifies the value of the parameter being accessed.The length depends on the format and can be a maximum of 4 bytes.00000000 hex – FFFFFFFF hex (i. e. 0dez – 4294967295dez )Content of PNU 0–PNU 999 (without PNU 202)Byte Designation Description0 Request Reference Request identification: Is echoed1 Response-ID Response ID: 01 hex : Read job (+)2 DO-ID Drive-Object-ID: Is echoed3 No. of Parameters Number of parameters: 01 hex4 Format Format: 0A hex (= 10 dez )5 No. of Values Number of values: 01 hex : value6 - 25 Value Value: Specifies the value of the parameter being accessedThe length depends on the format and can be a maximum of 20 bytes.Content of PNU 202