4 Commissioning4.4 Acyclic data52 DX-NET-SWD 06/13 MN04012009Z-EN www.eaton.comSmartWire-DT read response(+) – Parameter channel errorIf there is an error in the parameter channel, a positive SmartWire-DT readresponse(+) – Parameter channel error will be generated. The error will becontained either in a write job or a read job.The following table lists the PROFIdrive profile’s parameter channel errors.The possible errors for the DC1 variable frequency drive are marked(column DC1).Table 11: Parameter channel errors with PROFIdriveByte Designation Description0 Request Reference Request identification: Is echoed1 Response-ID Response ID: 81 hex : Read job(-); 82 hex: Write job(-)2 DO-ID Drive-Object-ID: Is echoed3 No. of Parameters Number of Parameters: 01 hex4 Format Format: 44 hex : Error5 No. of Values Number of values: 01 hex6 - 9 Error Number Fault number: 00 hex – 23hexFault-number[hex]Designation Description Supplemen-tary infor-mationDC100 Invalid parameter number Attempting to access a non-availableparameter0 ✓01 Parameter value cannot bechangedAttempting to have write access to aparameter that cannot be modifiedSubindex ✓02 Value below lower limit or aboveupper limitAttempting to have write access with avalue outside the value rangeSubindex ✓03 Bad subindex Attempting to access to a non-availablesubindex in a string or array parameterSubindex ✓04 Not an array Attempting to use a subindex in order toaccess a parameter without index005 Incorrect data type Attempting to access a parameter witha value not corresponding to theparameter’s data type0 ✓06 Setting not allowed Write access with a non-zero value notallowedSubindex ✓07 Description element cannot bemodifiedAttempting to have write access to adescription element that cannot bemodifiedSubindex08 reserved – –09 No description data available Attempting to access a non-availabledescription. The value is not available.0 ✓