4 Commissioning4.4 Acyclic data46 DX-NET-SWD 06/13 MN04012009Z-EN www.eaton.com4.4.3.3 Parameter P15 (PNU 423)SWD mode (P12 = 9 - 13)P-15 DI1 DI2 DI3/AI2 AI1/DI4 Notes0 0 = Blocked1 = Start enable0 = FWD1 = REV0 = Selected setpoint source1 = Fixed frequency 1 (P-20)Setpoint valueAI11 0 = Blocked1 = Start enable FWD0 = Selected setpointsource1 = Fixed frequency 1/20 = Fixed frequency 1 (P-20)1 = Fixed frequency 2 (P-21)Setpoint valueAI12 0 = Blocked1 = Start enable FWDDI2 DI3/AI2 DI3/AI2 Fixedfrequency0 = Fixedfrequency 1 - 4(P-20 - P-23)1 = maximumfrequency (P-01)4 selectable fixed frequen-cies:The analog input is used asdigital input.Switched at:8 V < Vinput < 30 V0 0 0 FF1 (P-20)1 0 0 FF2 (P-21)0 1 1 FF3 (P-22)1 1 1 FF4 (P-23)3 0 = Blocked1 = Start enable FWD0 = Selected setpointsource1 = Fixed frequency 1 (P-20)External fault:0 = Fault1 = RunSetpoint valueAI1Connection of an externalthermistor of type PT100 orsimilar to DI34 0 = Blocked1 = Start enable FWD0 = Analog input 11 = Analog input 2Setpoint value AI2 Setpoint valueAI1Changing between analoginput: 1 and 25 0 = Blocked1 = Start enable FWD0 = Blocked1 = Start enable REV0 = Selected setpoint source1 = Fixed frequency 1 (P-20)Setpoint valueAI1Connection of DI1 and DI2leads to a quick stop (P-24).6 0 = Blocked1 = Start enable0 = FWD1 = REVExternal fault:0 = Fault1 = EnableSetpoint valueAI1Connection of an externalthermistor of type PT100 orsimilar to DI37 0 = Blocked1 = Start enable FWD0 = Blocked1 = Start enable REVExternal fault:0 = Fault1 = EnableSetpoint valueAI1Connection of DI1 and DI2leads to a quick stop (P-24).8 0 = Blocked1 = Start enable0 = FWD1 = REVDI3/AI2 AI1/DI4 Fixed frequency0 0 FF1 (P-20)1 0 FF2 (P-21)0 1 FF3 (P-22)1 1 FF4 (P-23)9 0 = Blocked1 = Start enable FWD0 = Blocked1 = Start enable REVDI3/AI2 AI1/DI4 Fixed frequency Connection of DI1 and DI2leads to a quick stop (P-24).0 0 FF1 (P-20)1 0 FF2 (P-21)0 1 FF3 (P-22)1 1 FF4 (P-23)10 1 = Run FWD 0 = Stop 0 = Selected setpoint source1 = Fixed frequency 1 (P-20)Setpoint valueAI111 1 = Run FWD 0 = Stop 1 = Run REV Setpoint valueAI1Connection of DI1 and DI2leads to a quick stop (P-24).12 0 = Blocked1 = Start enable FWD0 = Quick stop (P-24)1 = Run FWD0 = Selected setpoint source1 = Fixed frequency 1 (P-20)Setpoint valueAI1Note: negative fixed frequencies are inverted it Run REV is selected.