4 Commissioning4.3 Cyclic dataDX-NET-SWD 06/13 MN04012009Z-EN www.eaton.com 314.3.4 Profile 2 (2 x 16 bit): Inputs (status)Input bytes 0 to 4 are mapped as follows on SmartWire-DT.Table 8: Profile 11: Input bytes 0 to 4Byte BIT Designation Meaning0 0, 1 – Not used2, 3 A1, A2 1-0-A-switch on DX-NET-SWD3:00: not defined10: Position A: Automatic (commands via SmartWire-DT/control signal terminal)01: Position 0: variable frequency drive stop11: Position 1: variable frequency drive operation4 DIAG 0: no diagnostic alarm1: Diagnostic alarm present5 – Not used6 PRSNT 0: Device not present1: Device present7 SUBST 0: Configured module present1: universal module M22-SWD-NOP(C) present1, 2 0 RSO Ready For Switching On: S20: Not ready for switching on1: Ready for switching on1 RDY Ready to operate; switched on: S30: not ready for operation1: ready for operation2 EN Enabled; operation: S40: Stop1: Operation3 ERR Error present0: no error1: Error4 C_Stop Free run-down, output de-energized (coast stop)0: no free run-down1: free run-down5 Q_Stop Quick stop, shortest ramp0: no quick stop1: Quick stop6 SOI Reclosing lockout (switching on inhibited: S1)0: No switch-on inhibit1: Switch-on inhibit7 WARN Warning present:0: no warning1: Warning8 f = f-ref operation at setpoint0: Ref. frequency not reached1. Ref. frequency reached9 Ctl_Req Control requested to PLCIs set if PNU 928.0 = 1 - 5.0: Not ready for remote control1: Ready for remote control