4 Commissioning4.4 Acyclic dataDX-NET-SWD 06/13 MN04012009Z-EN www.eaton.com 43975 5 ro UInt16 class info 1 Do not read-out975 6 ro UInt16 Supports Application Class 1976 0 rw UInt162100 0 rw U16 PI proportional gain P-41 1 - 300 10 ≙ 1.02101 0 rw U16 PI integral time constant P-42 0 - 300 10 ≙ 1.0 s2110 0 rw U16 Selection of the PI reference ofthe userP-44 0 - 1 0 : Preset digital setpoint value1: Analog input 12111 0 rw U16 PI digital reference P-45 0 - 1000 100 ≙ 10.0 %2112 0 rw U16 PI return selection P-46 0 - 3 0: Analog input 21: Analog input 12: Motor current2123 0 rw U16 PI operation mode P-43 0 - 1 0: direct operation1: Inverted operation2131 0 rw UInt16 PI feedback wake up level P-49 0 - 1000 900 = 90.0 %2204 0 rw U16 Brake switching enable P-34 0 - 2 Brake chopper activation(only for FS2 and FS3)0 : locked1: enabled with overloadprotection braking resistance2: enabled with overloadprotection braking resistance2221 0 rw U16 DC injection at stop P-32 0 - 250 250 ≙ 25.0 sPNU indexPNU subindex AccessrightDatatypeMeaning DisplaynumberValue Range Description