4 Commissioning4.4 Acyclic dataDX-NET-SWD 06/13 MN04012009Z-EN www.eaton.com 474.4.3.4 Fault numbersFaultnumber[hex]Value shown on display Description00 StoP Stop, ready for operation7112 OI-b Brake chopper overcurrent7114 OL-br Braking resistance overload2220 O-I • Overcurrent at variable frequency drive output• Motor overload• Overtemperature on variable frequency drive heat sink7131 I_t-trP Motor, thermal overload5400 PS-trP Internal fault (power section)3210 O_Vo I& Overvoltage (DC link)3220 V_Vo I& Undervoltage (DC link)4230 O-& Overtemperature (heat sink)4220 V-& Undertemperature (heat sink)6300 P-dEF Default settings (parameters have been loaded)9000 E-triP external error message7510 SC-trP Field bus error5130 reserved3130 P-LOSS Phase failure (mains side)2213 SPIn-F Motor pick-up control function (for catching spinning motors)failed4231 th-Flt Internal thermistor fault (heat sink)7601 dAtA-F EEPROM checksum fault7350 4-20 F Analog input:• Out-of-range value• Wire breakage (4-mA monitoring)