ParametersM-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com 87Drives Control, continuedNotes : P6.24, P6.26, P6.28 : P6.25, P6.27, P6.29In systems with mechanical resonances, you can cut out these frequency ranges for stationary operation.Up to three different frequency ranges can be set.PNU IDAccessRUN Value/Range DescriptionFactory Setting(P1.3)P6.24 509 X — Skip frequency 1, lower value 0.000.00–P6.25 Hz —P6.25 510 X — Skip frequency 1, upper value 0.00P6.24–P6.4 —P6.26 511 X — Skip frequency 2, lower value 0.000.00–P6.27 Hz —P6.27 512 X — Skip frequency 2, upper value 0.00P6.26–P6.4 Hz —P6.28 513 X — Skip frequency 3, lower value 0.000.00–P6.29 Hz —P6.29 514 X — Skip frequency 3, upper value 0.00P6.28–P6.4 Hz —Setting Range for Skip FrequenciesP6.30 759 X — Automatic REAF attempts 31–10 Define the permissible number of automatic restarts(REAF = Restart After Failure)P6.31 1481 X — Manual mode, primary control source 1Like P6.1 Assignment of the control levelsManual mode is activated via parameter P3.37P6.32 1482 X — Manual mode, primary speed reference 3Like P6.2 Assignment of setpoint sourcesManual mode is activated via parameter P3.37P6.33 1483 X — Manual mode, KEYPAD lock 1The Start/Stop functions are blocked in Manual mode via thekeypad0 Deactivated1 EnabledfHzt