ParametersM-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com 67Default I/OParameter Selection (P1)In the parameter selection (P1), you can choose between thefactory set quick configuration (P1.1 = 1) with a reducedparameter set and all parameters (P1.1 = 0).The setting of the parameters with the quick configuration(P1.1 = 1) is guided by a Quickstart Wizard. (A listing ofparameters is on Page 66.) Each executed parameter mustbe processed in succession up to frequency display M1.1.A return to a previous parameter is not possible here. Thepreset application parameters are selected under P1.2.Only when the quick start assistant (M1.1) is completed canthe parameters be called again and then also individually.With P1.1 = 0 (all parameters) and P1.2 = 0, 1, 2, or 3, youcan link the predefined application values with allparameters.Every single parameter value is reset to factory settingsevery time that the application menu is activated.Parameter SelectionsDesignation Terminal Function Parameter Designation Terminal Function ParameterDI1 8 Start Fwd P3.1, P3.2 DI6 16 PID Controller Deactivate P3.12DI2 9 Stop/Start Rev P3.1, P3.3 RO1 (NO) 22/23 Run P5.1, P5.10DI3 10 Fixed Frequency B0 (12 Hz) P3.9, P10.2 RO2 (NO/NC) 24/25/26 Fault P5.2, P5.11DI4 14 Fixed Frequency B1 (18 Hz) P3.10. P10.3 DO 13 Ready P5.3, P5.9DI5 15 Fault Reset P3.7PNU IDAccessRUNValue/Range DescriptionFactory Setting(P1.3)P1.1 115 — Quick start parameters 10 All parametersAll parameters are shown and can be changed. Exit from Quickstart.1 Only quick configuration parametersOnly the selected parameters of the quick configuration are shown and canbe changed (see Page 66 for list of parameters)P1.2 540 X — Application(See listing of the predefined application parameters in the table onPage 66)00 Basic1 Pump drive2 Fan drive3 High load (for example, hoisting or conveyor)P1.3 1472 X — Country specific default settings 10 EU (Europe, 50 Hz networks)1 NA (North America, 60 Hz networks)— The country specific factory setting takes into account the frequencybased parameters in relation to 50 and 60 Hz networks:PNU Designation P1.3 = 0 P1.3 = 1P6.4 Maximum frequency 50 Hz 60 HzP7.3 Motor, rated speed 1440 RPM 1720 RPMP7.6 Motor, rated frequency 50 Hz 60 HzP11.2 Cut-off frequency 50 Hz 60 HzP11.4 V/Hz characteristic curve, meanfrequency value25 Hz 30 HzP14.3 Motor (2PS) nominal speed 1440 RPM 1720 RPMP14.6 Motor (2PS) nominal frequency 50 Hz 60 HzP14.8 Maximum frequency (2PS) 50 Hz 60 Hz