6–8 469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUALCHAPTER 6: ACTUAL VALUESAny active alarms may be viewed here.The various alarm and alarm status actual values reflect the Alarm Name as programmedin the first line of the message. The status is “Active” if the condition that caused the alarmis still present.If the 469 chassis is only partially engaged with the case, the ALARM, 469 NOT INSERTEDPROPERLY service alarm appears after 1 second. Secure the chassis handle to ensure thatall contacts mate properly.MESSAGE REACTIVE POWERALARM: +2000 kvarRange: –50000 to +50000 kvarMESSAGE UNDERPOWERALARM: 200 kWRange: –50000 to +50000 kWMESSAGE TRIP COUNTERALARM: 25 TripsRange: 1 to 10000 TripsMESSAGE STARTER FAILURE:Trip Coil SuperRange: Trip Coil Super, WeldedContactor, Breaker FailureMESSAGE CURRENT DEMANDALARM: 1053 ARange: 1 to 10000 AMESSAGE kW DEMANDALARM: 505 kWRange: –50000 to +50000 kWMESSAGE kvar DEMANDALARM: –2000 kvarRange: –50000 to +50000 kvarMESSAGE kVA DEMANDALARM: 2062 kVARange: 0 to 50000 kVAMESSAGE ANALOG I/P 1ALARM: 201 UnitsRange: –50000 to +50000MESSAGE EMERGENCYRESTART:Range: Trip Still Present, Block StillPresent, No Trips & No BlocksMESSAGE ALARM, 469 NOTINSERTED PROPERLYRange: N/AMESSAGE 469 NOT IN SER-VICERange: Not Programmed, OutputRelays Forced, Analog OutputForced, Test Switch ShortedMESSAGE RTD #1HIRange: 1 to 250°CMESSAGE ANALOG 1-2ALARM: 50%Range: 0 to 999 (% Diff) or 0 to 99999(Abs Diff)MESSAGE ANALOG 3-4ALARM: 50%Range: 0 to 999 (% Diff) or 0 to 99999(Abs Diff)MESSAGE OVERTORQUEALARM:Range: 0.00 to 999999.9 Nm