6–30 469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUALCHAPTER 6: ACTUAL VALUES6.5 A4 Maintenance6.5.1 Trip CountersPATH: ACTUAL VALUES ZV A4 MAINTENANCE Z TRIP COUNTERSTRIP [Z]COUNTERSTOTAL NUMBER OFTRIPS: 0Range: 0 to 50000MESSAGE INCOMPLETESEQUENCERange: 0 to 50000. Caused by theReduced Voltage Start featureMESSAGE INPUT SWITCHTRIPS: 0Range: 0 to 50000 Caused by Remote,Speed, Load Shed, Pressure,Vibration, or General PurposeSwitch Trip featuresMESSAGE TACHOMETERTRIPS: 0Range: 0 to 50000. Caused by DigitalInput set as TachometerMESSAGE OVERLOADTRIPS: 0Range: 0 to 50000MESSAGE SHORT CIRCUITTRIPS: 0Range: 0 to 50000MESSAGE MECHANICAL JAMTRIPS: 0Range: 0 to 50000MESSAGE UNDERCURRENTTRIPS: 0Range: 0 to 50000MESSAGE CURRENT UNBALANCETRIPS: 0Range: 0 to 50000MESSAGE GROUND FAULTTRIPS: 0Range: 0 to 50000MESSAGE PHASE DIFFEREN-TIALRange: 0 to 50000MESSAGE ACCELERATIONTIMERRange: 0 to 50000MESSAGE STATOR RTDTRIPS: 0Range: 0 to 50000MESSAGE BEARING RTDTRIPS: 0Range: 0 to 50000MESSAGE OTHER RTDTRIPS: 0Range: 0 to 50000MESSAGE AMBIENT RTDTRIPS: 0Range: 0 to 50000MESSAGE UNDERVOLTAGETRIPS: 0Range: 0 to 50000