Appendix D. Setting Up the System RackBefore setting up a rack, check through the following specifications and clearances, then go to “Model 6C3Rack Installation Inventory” on page 405.Rack SpecificationsThis section contains specifications for the system rack.7014 Model T00 and T42 RackThe mechanical packaging, cooling, power supply, and environmental specifications for the rack are shownin the following table:DimensionsHeight 1804 mm 71.0 in.Capacity 36 EIA UnitsWith PDP - DC only 1926 mm 75.8 in.Width without sidepanels623 mm 24.5 in.With side panels 644 mm 25.4 in.Depth with rear door 1042 mm 41.0 in.RS/6000 T00 withboth doors1098 mm 43.3 in.pSeries T00 with bothdoors1147 mm 45.2 in.WeightBase Rack 244 kg 535 lbsFull Rack¹ 816 kg 1795 lbs.Electrical² (sum specified values fordrawers or enclosures in rack)AC RackPower source loadingmaximum in kVA (perPDB)⁴4.8Voltage range (V ac) 200 to 240Frequency (hertz) 50 or 60TemperatureRequirements(see specifications for drawers or enclosures)HumidityRequirements(see specifications for drawers or enclosures)Noise Emissions (see specifications for drawers or enclosures)Clearances Front Back Left RightInstall/Air Flow Maintenance of a proper service clearance should allow proper airflow.Service 915mm(36 in) 915mm(36 in) 915mm(36 in) 915mm(36 in)1. Configuration dependent, base rack weight plus the weight of the drawers mounted in the rack. The rack cansupport up to a maximum weight of 35 lbs/EIA Unit.2. The total rack power should be derived from the sum of the power used by the drawers in the rack.3. Each AC Power Distribution Bus (PDB) can supply 4.8 kVA. A rack can have up to four PDB’s as required by thedrawers mounted in the rack.403