4.6 Application SelectionYASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual 103Start-Up Programming& Operation44.6 Application SelectionSeveral Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of theseApplication Presets automatically assigns functions to the input and output terminals, and sets certain parameters tovalues appropriate for the application that was selected. In addition, the parameters most likely to be changed areassigned to the group of User Parameters, A2-01 through A2-16. User Parameters are part of the Setup Group, andprovide quicker access to by eliminating the need to scroll through multiple menus.An Application Preset can either be selected from the Application Selection display in the Setup Group (Refer toSimplified Setup Using the Setup Group on page 95) or in parameter A1-06. The following presets can be selected:Note: An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary toinitialize the drive by setting A1-03 to “2220” or “3330” prior to selecting an Application Preset.WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may changethe I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.◆ Setting 1: Water Supply Pump ApplicationTable 4.5 Water Supply Pump: Parameter SettingsTable 4.6 Water Supply Pump: User Parameters (A2-01 to A2-16)◆ Setting 2: Conveyor ApplicationTable 4.7 Conveyor: Parameter SettingsNo. Parameter Name Setting Range DefaultA1-06 Application Presets0: Disabled1: Water supply pump2: Conveyor3: Exhaust fan4: HVAC5: Compressor6: Hoist7: Crane0No. Name Default SettingA1-02 Control Method Selection 0: V/f Controlb1-04 Reverse Operation Selection 1: Reverse ProhibitedC1-01 Acceleration Time 1 1.0 sC1-02 Deceleration Time 1 1.0 sC6-01 Duty Rating 1: Normal DutyE1-03 V/f Pattern Selection 0FHE1-07 Mid Output Frequency 30.0 HzE1-08 Mid Output Frequency Voltage 50.0 VL2-01 Momentary Power Loss Operation Selection 1: EnabledL3-04 Stall Prevention Selection during Deceleration 1: EnabledNo. Parameter Name No. Parameter Nameb1-01 Frequency Reference Selection E1-08 Mid Output Frequency Voltageb1-02 Run Command Selection E2-01 Motor Rated Currentb1-04 Reverse Operation Selection H1-05 Multi-Function Digital Input Terminal S5 Function SelectionC1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function SelectionC1-02 Deceleration Time 1 H1-07 Multi-Function Digital Input Terminal S7 Function SelectionE1-03 V/f Pattern Selection L5-01 Number of Auto Restart AttemptsE1-07 Mid Output Frequency − −No. Parameter Name Default SettingA1-02 Control Method Selection 0: V/f ControlC1-01 Acceleration Time 1 3.0 sC1-02 Deceleration Time 1 3.0 sC6-01 Duty Rating 0: Heavy DutyL3-04 Stall Prevention Selection during Deceleration 1: Enabled