400 YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical ManualB.3 Parameter TableB.3 Parameter Table◆ A: Initialization ParametersThe A parameter group creates the operating environment for the drive. This includes the parameter Access Level, MotorControl Method, Password, User Parameters and more.■ A1: Initialization Parameters■ A2: User ParametersNo.(Addr.) Name Description Setting PageA1-00(100H)<3><2> Default setting value is dependent on the Application Preset selected with parameter A1-06.<3> Parameter setting value is not reset to the default value when the drive is initialized.Language Selection0: English1: Japanese2: German3: French4: Italian5: Spanish6: Portuguese7: ChineseDefault: 0Min: 0Max: 7130A1-01(101H)<2>Access Level Selection 0: View and set A1-01 and A1-04. U- parameters can also be viewed.1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)2: Advanced Access (access to view and set all parameters)Default: 2Min: 0Max: 2130A1-02(102H)<3>Control Method Selection0: V/f Control1: V/f Control with PG2: Open Loop Vector Control3: Closed Loop Vector Control5: Open Loop Vector Control for PM6: Advanced Open Loop Vector Control for PM7: Closed Loop Vector Control for PMDefault: 0Min: 0Max: 7130A1-03(103H) Initialize Parameters0: No initialization1110: User Initialize (parameter values must be stored using parameter o2-03)2220: 2-wire initialization3330: 3-wire initialization5550: oPE04 error resetDefault: 0Min: 0Max: 5550131A1-04(104H) PasswordWhen the value set into A1-04 does not match the value set into A1-05, parameters A1-01through A1-03, A1-06, and A2-01 through A2-33 cannot be changed.Default: 0000Min: 0000Max: 9999132A1-05(105H) Password SettingA1-06(127H) Application Preset0: General-purpose1: Water supply pump2: Conveyor3: Exhaust fan4: HVAC fan5: Air compressor6: Elevator7: HoistDefault: 0Min: 0Max: 7134A1-07(128H) DriveWorksEZ Function Selection 0: DWEZ disabled1: DWEZ enabled2: Digital input (enabled when H1- = 9F)Default: 0Min: 0Max: 2134No.(Addr.) Name Description Setting PageA2-01 toA2-32(106 to 125H)<1> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not equal 0.<2> Default setting value is determined by the Application Preset selected with parameter A1-06.User Parameters 1 to 32 Parameters that were recently edited are listed here. The user can also select parameters toappear here for quick access.Default: <2>Min: b1-01Max: o2-08135A2-33(126H)User Parameter AutomaticSelection 0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access.Default: 1 <1>Min: 0Max: 1135All Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonly