4.6 Application Selection104 YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical ManualTable 4.8 Conveyor: User Parameters (A2-01 to A2-16)◆ Setting 3: Exhaust Fan ApplicationTable 4.9 Exhaust Fan: Parameter SettingsTable 4.10 Exhaust Fan: User Parameters (A2-01 to A2-16)◆ Setting 4: HVAC Fan ApplicationTable 4.11 HVAC Fan: Parameter SettingsTable 4.12 HVAC Fan: User Parameters (A2-01 to A2-16)No. Parameter Name No. Parameter NameA1-02 Control Method Selection C1-02 Deceleration Time 1b1-01 Frequency Reference Selection E2-01 Motor Rated Currentb1-02 Run Command Selection L3-04 Stall Prevention Selection during DecelerationC1-01 Acceleration Time 1 − −No. Parameter Name Default SettingA1-02 Control Method Selection 0: V/f Controlb1-04 Reverse Operation Selection 1: Reverse ProhibitedC6-01 Duty Selection 1: Normal DutyE1-03 V/f Pattern Selection 0FHE1-07 Mid Output Frequency 30.0 HzE1-08 Mid Output Frequency Voltage 50.0 VL2-01 Momentary Power Loss Operation Selection 1: EnabledL3-04 Stall Prevention Selection during Deceleration 1: EnabledNo. Parameter Name No. Parameter Nameb1-01 Frequency Reference Selection E1-07 Mid Output Frequencyb1-02 Run Command Selection E1-08 Mid Output Frequency Voltageb1-04 Reverse Operation Selection E2-01 Motor Rated Currentb3-01 Speed Search Selection at Start H1-05 Multi-Function Digital Input Terminal S5 Function SelectionC1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function SelectionC1-02 Deceleration Time 1 H1-07 Multi-Function Digital Input Terminal S7 Function SelectionE1-03 V/f Pattern Selection L5-01 Number of Auto Restart AttemptsNo. Parameter Name Default SettingA1-02 Control Method Selection 0: V/f Controlb1-04 Reverse Operation Selection 1: Reverse Prohibitedb1-17 Run Command at Power Up 1: Run command issued, motor operation startC6-01 Duty Rating 1: Normal DutyC6-02 Carrier Frequency Selection 3: 8.0 kHzH2-03 Terminals P2 Function Selection 39: Watt Hour Pulse OutputL2-01 Momentary Power Loss Operation Selection 2: CPU Power Active - Drive will restart if power returns prior to control powersupply shut down.L8-03 Overheat Pre-Alarm Operation Selection 4: Operation at lower speedL8-38 Carrier Frequency Reduction 2: Enabled across entire frequency range.No. Parameter Name No. Parameter Nameb1-01 Frequency Reference Selection d2-02 Frequency Reference Lower Limitb1-02 Run Command Selection E1-03 V/f Pattern Selectionb1-03 Stopping Method Selection E1-04 Max Output Frequencyb1-04 Reverse Operation Selection E2-01 Motor Rated CurrentC1-01 Acceleration Time 1 H3-11 Terminal A2 Gain SettingC1-02 Deceleration Time 1 H3-12 Terminal A2 Input BiasC6-02 Carrier Frequency Selection L2-01 Momentary Power Loss Operation Selectiond2-01 Frequency Reference Upper Limit o4-12 kWh Monitor Initial Value Selection