B.3 Parameter Table414 YASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual■ d7: Offset Frequency◆ E: Motor Parameters■ E1: V/f Pattern for Motor 1No.(Addr.) Name Description Setting Paged7-01(2B2H) Offset Frequency 1 Added to the frequency reference when the digital input “Frequency offset 1” (H1- = 44) isswitched on.Default: 0.0%Min: -100.0%Max: 100.0%193d7-02(2B3H) Offset Frequency 2 Added to the frequency reference when the digital input “Frequency offset 2” (H1- = 45) isswitched on.Default: 0.0%Min: -100.0%Max: 100.0%193d7-03(2B4H) Offset Frequency 3 Added to the frequency reference when the digital input “Frequency offset 3” (H1- = 46) isswitched on.Default: 0.0%Min: -100.0%Max: 100%193No.(Addr.) Name Description Setting PageE1-01(300H)<3> Parameter setting value is not reset to the default value when the drive is initialized.<4> Default setting is dependent on the control mode (A1-02), the drive model (o2-04), and the Drive Duty (C6-01).<14> Default setting value is dependent on the motor code set to E5-01.Input Voltage Setting This parameter must be set to the power supply voltage.WARNING! Drive input voltage (not motor voltage) must be set in E1-01 for the protectivefeatures of the drive to function properly. Failure to do so may result in equipment damage and/or death or personal injury.Default: 200 V <18>Min: 155 VMax: 255 V194E1-03(302H) V/f Pattern Selection0: 50 Hz, Constant torque 11: 60 Hz, Constant torque 22: 60 Hz, Constant torque 3 (50 Hz base)3: 72 Hz, Constant torque 4 (60 Hz base)4: 50 Hz, Variable torque 15: 50 Hz, Variable torque 26: 60 Hz, Variable torque 37: 60 Hz, Variable torque 48: 50 Hz, High starting torque 19: 50 Hz, High starting torque 2A: 60 Hz, High starting torque 3B: 60 Hz, High starting torque 4C: 90 Hz (60 Hz base)D: 120 Hz (60 Hz base)E: 180 Hz (60 Hz base)F: Custom V/f, E1-04 through E1-13 settings define the V/f patternDefault: F <3>Min: 0Max: F <30>194E1-04(303H) Maximum Output FrequencyThese parameters are only applicable when E1-03 is set to F.To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, thesetting for E1-08 will be disregarded. Ensure that the four frequencies are set according to theserules:E1-09 ≤ E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above conditions do notapply.Note: Some parameters may not be available depending on the control mode.• E1-07, E1-08 and E-10 are available only in the following control modes: V/f Control, V/fwith PG, Open Loop Vector.• E1-11, E1-12 and E-13 are available only in the following control modes: V/f Control, V/fwith PG, Open Loop Vector, Closed Loop Vector.Default: <4> <14>Min: 40.0Max: 400.0 <29>197E1-05(304H) Maximum VoltageDefault: <4> <14> <18>Min: 0.00 VMax: 255.0 V <18>197E1-06(305H) Base FrequencyDefault: <4> <14>Min: 0.0Max: E1-04 <29>197E1-07(306H) Middle Output FrequencyDefault: <4>Min: 0.0Max: E1-04197E1-08(307H) Middle Output Frequency VoltageDefault: <4> <18>Min: 0.0 VMax: 255.0 V <18>197E1-09(308H) Minimum Output FrequencyDefault: <4> <14>Min: 0.0Max: E1-04 <26> <29>197E1-10(309H)Minimum Output FrequencyVoltageDefault: <4> <18>Min: 0.0 VMax: 255.0 V <18>197E1-11(30AH)<21>Middle Output Frequency 2Default: 0.0 HzMin: 0.0Max: E1-04 <26>197E1-12(30BH)<21>Middle Output Frequency Voltage2Default: 0.0 VMin: 0.0 VMax: 255.0 V <18>197E1-13(30CH) Base VoltageDefault: 0.0 V<18> <27>Min: 0.0 VMax: 255.0 V <18>197All Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyAll Modes common_TMonlyOLV/PM AOLV/PMCLVV/f w/PGCLV/PMV/f OLV common_TMonlyAll Modes common_TMonlyOutput Voltage (V)Frequency (Hz)E1-05E1-12E1-13E1-08E1-10E1-09 E1-07 E1-06 E1-11 E1-04