4.6 Application SelectionYASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual 105Start-Up Programming& Operation4◆ Setting 5: Compressor ApplicationTable 4.13 Compressor: Parameter SettingsTable 4.14 Compressor: User Parameters (A2-01 to A2-16):◆ Setting 6: Hoist ApplicationNote: 1. Read the instructions listed on page 106 when using Hoist Application Preset2. Perform Auto-Tuning after selecting the Hoist Application Preset.Table 4.15 Hoist: Parameters and SettingsTable 4.16 Hoist: User Parameters (A2-01 to A2-16):No. Parameter Name Default SettingA1-02 Control Method Selection 0: V/f Controlb1-04 Reverse Operation Selection 1: Reverse ProhibitedC1-01 Acceleration Time 1 5.0 sC1-02 Deceleration Time 1 5.0 sC6-01 Duty Rating 0: Heavy DutyE1-03 V/f Pattern Selection 0FHL2-01 Momentary Power Loss Operation Selection 1: EnabledL3-04 Stall Prevention Selection during Deceleration 1: EnabledNo. Parameter Name No. Parameter Nameb1-01 Frequency Reference Selection E1-03 V/f Pattern Selectionb1-02 Run Command Selection E1-07 Mid Output Frequencyb1-04 Reverse Operation Selection E1-08 Mid Output Frequency VoltageC1-01 Acceleration Time 1 E2-01 Motor Rated CurrentC1-02 Deceleration Time 1 − −No. Parameter Name Default SettingA1-02 Control Method Selection 2: Open Loop Vector Controlb1-01 Frequency Reference Selection 0: Operatorb6-01 Dwell Reference at Start 3.0 Hzb6-02 Dwell Time at Start 0.3 sC1-01 Acceleration Time 1 3.0 sC1-02 Deceleration Time 1 3.0 sC6-01 Duty Rating 0: Heavy DutyC6-02 Carrier Frequency Selection 2: 5 kHzd1-01 Frequency Reference 1 6.0 Hzd1-02 Frequency Reference 2 30.0 Hzd1-03 Frequency Reference 3 50. 0 HzE1-03 V/f Pattern Selection 0FHH2-01 Terminals M1-M2 Function Selection 5: Frequency Detection 2H2-02 Terminals M3-M4 Function Selection 37: During Frequency OutputL2-03 Momentary Power Loss Minimum Baseblock Time 0.3 sL3-04 Momentary Power Loss Voltage Recovery Ramp Time 0: DisabledL4-01 Speed Agreement Detection Level 2.0 HzL4-02 Speed Agreement Detection Width 0.0 HzL6-01 Torque Detection Selection 1 8: UL3 at RUN - FaultL6-02 Torque Detection Level 1 2%L6-03 Torque Detection Time 1 0.5 sL8-05 Input Phase Loss Protection Selection 1: EnabledL8-07 Output Phase Loss Protection 1: EnabledL8-38 Carrier Frequency Reduction 1: Enabled below 6 HzL8-41 Current Alarm Selection 1: Enabled (alarm is output)No. Parameter Name No. Parameter NameA1-02 Control Method Selection d1-02 Frequency Reference 2b1-01 Frequency Reference Selection d1-03 Frequency Reference 3b6-01 Dwell Reference at Start E1-08 Mid Output Frequency Voltageb6-02 Dwell Time at Start H2-01 Terminals M1-M2 Function SelectionC1-01 Acceleration Time 1 L1-01 Motor Overload Protection SelectionC1-02 Deceleration Time 1 L4-01 Speed Agreement Detection LevelC6-02 Carrier Frequency Selection L6-02 Torque Detection Level 1d1-01 Frequency Reference 1 L6-03 Torque Detection Time 1