5.10 o: Operator Related SettingsYASKAWA ELECTRIC SIEP C710616 27C YASKAWA AC Drive A1000 Technical Manual 287Parameter Details5■ o2-06: Operation Selection when Digital Operator is DisconnectedDetermines if the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set to0. When the operator is reconnected, the display will indicate that it was disconnected.Setting 0: Continue operationThe operation is continued.Setting 1: Trigger a faultThe operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.■ o2-07: Motor Direction at Power Up when Using OperatorDetermines the direction the motor will rotate after the drive is powered up and the Run command is given from thedigital operator.Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).Setting 0: ForwardSetting 1: Reverse◆ o3: Copy FunctionThese parameters control the digital operator’s Copy function. The Copy function lets the user store all parametersettings into the memory of the digital operator, and easily transfer those settings to other drives (requires that the otherdrives be the same model, capacity, and have the same control mode setting). See Copy Function Related Displays onpage 332 for a description of errors and displays.■ o3-01 Copy Function SelectionSetting o3-01 will instruct the drive to Read, Write, or Verify parameters settings.0: Copy Select (no function)1: INV --> OP READAll parameters are copied from the drive to the digital operator.Note: The copy protection for the digital operator is enabled by default. To unlock copy protection, set o3-01 = 1.2: OP --> INV WRITEAll parameters are copied from the digital operator to the drive.3: OP<-->INV VERIFYParameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.■ o3-02 Copy Allowed SelectionRestricts or allows the use of the Copy function.0: Disabled1: EnabledNo. Name Setting Range Defaulto2-06 Digital Operator Disconnection Operation 0 or 1 0No. Name Setting Range Defaulto2-07 Motor Direction at Power Up when Using Operator 0 or 1 0No. Name Setting Range Defaulto3-01 Copy Function Selection 0 to 3 0No. Name Setting Range Defaulto3-02 Copy Allowed Selection 0 or 1 0