Table 103:GUPPDUP Group settings (advanced)Name Values (Range) Unit Step Default Descriptionk 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for powermeasurement, U and ITable 104:GUPPDUP Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global BaseValue groupsMode L1, L2, L3AronePos SeqL1L2L2L3L3L1L1L2L3- - Pos Seq Mode of measurement for current andvoltage7.7.3.5 Monitored dataTable 105:GUPPDUP Monitored dataName Type Values (Range) Unit DescriptionP REAL - MW Active PowerPPERCENT REAL - % Active power in % ofcalculated power basevalueQ REAL - MVAr Reactive powerQPERCENT REAL - % Reactive power in % ofcalculated power basevalue7.7.4 Operation principleA simplified scheme showing the principle of the power protection function isshown in figure 102. The function has two stages with individual settings.1MRK 502 034-UEN - Section 7Current protection197Technical Manual