11.2.2.4 SignalsTable 186:QCBAY Input signalsName Type Default DescriptionLR_OFF BOOLEAN 0 External Local/Remote switch is in Off positionLR_LOC BOOLEAN 0 External Local/Remote switch is in Local positionLR_REM BOOLEAN 0 External Local/Remote switch is in RemotepositionLR_VALID BOOLEAN 0 Data representing the L/R switch position is validBL_UPD BOOLEAN 0 Steady signal to block the position updatesBL_CMD BOOLEAN 0 Steady signal to block the commandTable 187:QCBAY Output signalsName Type DescriptionPSTO INTEGER Value for the operator place allocationUPD_BLKD BOOLEAN Update of position is blockedCMD_BLKD BOOLEAN Function is blocked for commandsLOC BOOLEAN Local operation allowedREM BOOLEAN Remote operation allowed11.2.2.5 SettingsTable 188:QCBAY Non group settings (basic)Name Values (Range) Unit Step Default DescriptionAllPSTOValid PriorityNo priority- - Priority Priority of originators11.2.3 Local remote LOCREM11.2.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote LOCREM - -11.2.3.2 FunctionalityThe signals from the local HMI or from an external local/remote switch are appliedvia the function blocks LOCREM and LOCREMCTRL to the Bay control(QCBAY) function block. A parameter in function block LOCREM is set tochoose if the switch signals are coming from the local HMI or from an externalhardware switch connected via binary inputs.1MRK 502 034-UEN - Section 11Control293Technical Manual