Name Values (Range) Unit Step Default DescriptiontSCA 0.000 - 60.000 s 0.001 0.100 Time delay for synchrocheck AutotSCM 0.000 - 60.000 s 0.001 0.100 Time delay for synchrocheck ManualAutoEnerg OffDLLBDBLLBoth- - DBLL Automatic energizing check modeManEnerg OffDLLBDBLLBoth- - Both Manual energizing check modeManEnergDBDL OffOn- - Off Manual dead bus, dead line energizingtAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizingchecktManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing checkTable 183:SESRSYN Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global BaseValue groupsMeasVoltLine1 UL1UL1L2PosSeq- - UL1 Measured voltage for Line 1MeasVoltBus1 UL1UL1L2PosSeq- - UL1 Measured voltage for Busbar 1MeasVoltBus2 UL1UL1L2PosSeq- - UL1 Measured voltage for Busbar 211.1.6 Monitored dataTable 184:SESRSYN Monitored dataName Type Values (Range) Unit DescriptionUDIFFME REAL - kV Calculated difference involtageFRDIFFME REAL - Hz Calculated difference infrequencyPHDIFFME REAL - deg Calculated difference ofphase angle1MRK 502 034-UEN - Section 11Control285Technical Manual