11.6.5 SettingsTable 206:SPC8GGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnLatched1 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 1tPulse1 0.01 - 6000.00 s 0.01 0.10 Output1 Pulse TimeLatched2 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 2tPulse2 0.01 - 6000.00 s 0.01 0.10 Output2 Pulse TimeLatched3 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 3tPulse3 0.01 - 6000.00 s 0.01 0.10 Output3 Pulse TimeLatched4 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 4tPulse4 0.01 - 6000.00 s 0.01 0.10 Output4 Pulse TimeLatched5 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 5tPulse5 0.01 - 6000.00 s 0.01 0.10 Output5 Pulse TimeLatched6 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 6tPulse6 0.01 - 6000.00 s 0.01 0.10 Output6 Pulse TimeLatched7 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 7tPulse7 0.01 - 6000.00 s 0.01 0.10 Output7 Pulse TimeLatched8 PulsedLatched- - Pulsed Setting for pulsed/latched mode foroutput 8tPulse8 0.01 - 6000.00 s 0.01 0.10 Output8 pulse time11.6.6 Operation principleThe PSTO input will determine which the allowed position for the operator(LOCAL, REMOTE, ALL) is. Upon sending a command from an allowed operatorposition, one of the 8 outputs will be activated. The settings Latchedx and tPulsex(where x is the respective output) will determine if the signal will be pulsed (andhow long the pulse is) or latched (steady). BLOCK will block the operation of thefunction – in case a command is sent, no output will be activated.PSTO is the universal operator place selector for all controlfunctions. Even if PSTO can be configured to allow LOCAL orALL operator positions, the only functional position usable with theSPC8GGIO function block is REMOTE.1MRK 502 034-UEN - Section 11Control307Technical Manual