Name Type Default Description76_TRANS BOOLEAN 0 Information number 76, signal transmitted77_RECEV BOOLEAN 0 Information number 77, signal received78_ZONE1 BOOLEAN 0 Information number 78, zone 179_ZONE2 BOOLEAN 0 Information number 79, zone 280_ZONE3 BOOLEAN 0 Information number 80, zone 381_ZONE4 BOOLEAN 0 Information number 81, zone 482_ZONE5 BOOLEAN 0 Information number 82, zone 584_STGEN BOOLEAN 0 Information number 84, start general85_BFP BOOLEAN 0 Information number 85, breaker failure86_MTRL1 BOOLEAN 0 Information number 86, trip measuring systemphase L187_MTRL2 BOOLEAN 0 Information number 87, trip measuring systemphase L288_MTRL3 BOOLEAN 0 Information number 88, trip measuring systemphase L389_MTRN BOOLEAN 0 Information number 89, trip measuring systemneutral N90_IOC BOOLEAN 0 Information number 90, over current trip, stage low91_IOC BOOLEAN 0 Information number 91, over current trip, stage high92_IEF BOOLEAN 0 Information number 92, earth-fault trip, stage low93_IEF BOOLEAN 0 Information number 93, earth-fault trip, stage highARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)FLTLOC BOOLEAN 0 Faultlocator faultlocation valid (LMBRFLO-CALCMADE)13.20.4 SettingsTable 358:I103FLTPROT Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 128 Function type (1-255)13.21 IED status for IEC 60870-5-103 I103IED13.21.1 FunctionalityI103IED is a function block with defined IED functions in monitor direction. Thisblock uses parameter as FunctionType, and information number parameter isdefined for each input signal.1MRK 502 034-UEN - Section 13Monitoring449Technical Manual