11.2.3.3 Function blockLOCREMCTRLOFFLOCCTRLREMCTRLLHMICTRLOFFLOCALREMOTEVALIDIEC09000076_1_en.vsdIEC09000076 V1 ENFigure 149: LOCREM function block11.2.3.4 SignalsTable 189:LOCREM Input signalsName Type Default DescriptionCTRLOFF BOOLEAN 0 Disable controlLOCCTRL BOOLEAN 0 Local in controlREMCTRL BOOLEAN 0 Remote in controlLHMICTRL INTEGER 0 LHMI controlTable 190:LOCREM Output signalsName Type DescriptionOFF BOOLEAN Control is disabledLOCAL BOOLEAN Local control is activatedREMOTE BOOLEAN Remote control is activatedVALID BOOLEAN Outputs are valid11.2.3.5 SettingsTable 191:LOCREM Non group settings (basic)Name Values (Range) Unit Step Default DescriptionControlMode Internal LR-switchExternal LR-switch- - Internal LR-switch Control mode for internal/external LR-switch11.2.4 Local remote control LOCREMCTRL11.2.4.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote control LOCREMCTRL - -Section 11 1MRK 502 034-UEN -Control294Technical Manual