7.9.5 SettingsTable 115:NS2PTOC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OntAlarm 0.00 - 6000.00 s 0.01 3.00 Time delay for Alarm (operated bySTART signal), in secOpStep1 OffOn- - On Enable execution of step 1I2-1> 3 - 500 %IB 1 10 Step 1 Neg. Seq. Current pickup level, in% of IBaseCurveType1 DefiniteInverse- - Definite Selection of definite or inverse time-characteri. for step 1t1 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 1, in sectResetDef1 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer ofstep 1, in secK1 1.0 - 99.0 s 0.1 10.0 Neg. seq. capability value of generatorfor step 1, in sect1Min 0.000 - 60.000 s 0.001 5.000 Minimum trip time for inverse delay ofstep 1, in sect1Max 0.00 - 6000.00 s 0.01 1000.00 Maximum trip delay for step 1, in secResetMultip1 0.01 - 20.00 - 0.01 1.00 Reset multiplier for K1, defines resettime of inverse curveOpStep2 OffOn- - On Enable execution of step 2I2-2> 3 - 500 %IB 1 10 Step 2 Neg. Seq. Current pickup level, in% of IBaset2 0.00 - 6000.00 s 0.01 10.00 Definite time delay for trip of step 2, in sectResetDef2 0.000 - 60.000 s 0.001 0.000 Time delay for reset of definite timer ofstep 2, in secTable 116:NS2PTOC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global BaseValue groups7.9.6 Monitored dataTable 117:NS2PTOC Monitored dataName Type Values (Range) Unit DescriptionNSCURR REAL - A Negative sequencecurrent in primary ampsSection 7 1MRK 502 034-UEN -Current protection206Technical Manual