Name Values (Range) Unit Step Default DescriptionU1HiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)U1HiLim 0 - 2000000 V 1 86000 High limit (physical value)U1LowLim 0 - 2000000 V 1 71000 Low limit (physical value)U1LowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limitsU2ZeroDb 0 - 100000 m% 1 500 Zero point clampingU2HiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)U2HiLim 0 - 2000000 V 1 86000 High limit (physical value)U2LowLim 0 - 2000000 V 1 71000 Low limit (physical value)U2LowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)13.4.6.5 Monitored dataTable 302:VMSQI Monitored dataName Type Values (Range) Unit Description3U0 REAL - kV 3U0 Amplitude3U0ANGL REAL - deg 3U0 AngleU1 REAL - kV U1 AmplitudeU1ANGL REAL - deg U1 AngleU2 REAL - kV U2 AmplitudeU2ANGL REAL - deg U2 Angle13.4.7 Phase-neutral voltage measurement VNMMXU13.4.7.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPhase-neutral voltage measurement VNMMXUUSYMBOL-UU V1 EN-13.4.7.2 Function blockThe available function blocks of an IED are depending on the actual hardware(TRM) and the logic configuration made in PCM600.1MRK 502 034-UEN - Section 13Monitoring367Technical Manual