Name Type DescriptionI2 REAL I2 AmplitudeI2RANG INTEGER I2 Amplitude rangeI2ANGL REAL I2Angle13.4.5.4 SettingsTable 295:CMSQI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / On3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %s3I0Min 0 - 500000 A 1 0 Minimum value3I0Max 0 - 500000 A 1 3300 Maximum value3I0RepTyp CyclicDead bandInt deadband- - Dead band Reporting type3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sI1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sI1Min 0 - 500000 A 1 0 Minimum valueI1Max 0 - 500000 A 1 1300 Maximum valueI1RepTyp CyclicDead bandInt deadband- - Dead band Reporting typeI1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sI2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sI2Min 0 - 500000 A 1 0 Minimum valueI2Max 0 - 500000 A 1 1300 Maximum valueI2RepTyp CyclicDead bandInt deadband- - Dead band Reporting typeI2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limitsI2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %s1MRK 502 034-UEN - Section 13Monitoring363Technical Manual