15.8.2 FunctionalityGOOSESPRCV is used to receive a single point value from the sender usingIEC61850 protocol over GOOSE.15.8.3 Function blockGOOSESPRCVBLOCK ^SPOUTDATAVALIDCOMMVALIDTESTIEC10000248-1-en.vsdIEC10000248 V1 ENFigure 235: GOOSESPRCV function block15.8.4 SignalsTable 394:GOOSESPRCV Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionTable 395:GOOSESPRCV Output signalsName Type DescriptionSPOUT BOOLEAN Single point outputDATAVALID BOOLEAN Data valid for single point outputCOMMVALID BOOLEAN Communication valid for single point outputTEST BOOLEAN Test output15.8.5 SettingsTable 396:GOOSESPRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On15.8.6 Operation principleThe DATAVALID output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does not happen.The TEST output will go HIGH if the sending IED is in test mode.Section 15 1MRK 502 034-UEN -Station communication476Technical Manual