Table 286:CMMXU Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionILZeroDb 0 - 100000 m% 1 500 Zero point clampingILHiHiLim 0 - 500000 A 1 1200 High High limit (physical value)ILHiLim 0 - 500000 A 1 1100 High limit (physical value)ILLowLim 0 - 500000 A 1 0 Low limit (physical value)ILLowLowLim 0 - 500000 A 1 0 Low Low limit (physical value)ILMin 0 - 500000 A 1 0 Minimum valueILLimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limitsIAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at5% of IrIAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at30% of IrIAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at100% of IrIAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of IrIAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of IrIAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir13.4.3.5 Monitored dataTable 287:CMMXU Monitored dataName Type Values (Range) Unit DescriptionIL1 REAL - A IL1 AmplitudeIL1ANGL REAL - deg IL1 AngleIL2 REAL - A IL2 AmplitudeIL2ANGL REAL - deg IL2 AngleIL3 REAL - A IL3 AmplitudeIL3ANGL REAL - deg IL3 Angle13.4.4 Phase-phase voltage measurement VMMXU13.4.4.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPhase-phase voltage measurement VMMXUUSYMBOL-UU V1 EN-1MRK 502 034-UEN - Section 13Monitoring359Technical Manual