13.17 Measurands user defined signals for IEC60870-5-103 I103MEASUSR13.17.1 FunctionalityI103MEASUSR is a function block with user defined input measurands in monitordirection. These function blocks include the FunctionType parameter for eachblock in the private range, and the Information number parameter for each block.13.17.2 Function blockIEC10000288-1-en.vsdI103MEASUSRBLOCK^INPUT1^INPUT2^INPUT3^INPUT4^INPUT5^INPUT6^INPUT7^INPUT8^INPUT9IEC10000288 V1 ENFigure 219: I103MEASUSR function block13.17.3 SignalsTable 351:I103MEASUSR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingINPUT1 REAL 0.0 Service value for measurement on input 1INPUT2 REAL 0.0 Service value for measurement on input 2INPUT3 REAL 0.0 Service value for measurement on input 3INPUT4 REAL 0.0 Service value for measurement on input 4INPUT5 REAL 0.0 Service value for measurement on input 5INPUT6 REAL 0.0 Service value for measurement on input 6INPUT7 REAL 0.0 Service value for measurement on input 7INPUT8 REAL 0.0 Service value for measurement on input 8INPUT9 REAL 0.0 Service value for measurement on input 9Section 13 1MRK 502 034-UEN -Monitoring444Technical Manual