Name Type DescriptionP30 BOOLEAN Selector switch position 30P31 BOOLEAN Selector switch position 31P32 BOOLEAN Selector switch position 32SWPOSN INTEGER Switch position as integer value11.3.5 SettingsTable 197:SLGGIO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnNrPos 2 - 32 - 1 32 Number of positions in the switchOutType PulsedSteady- - Steady Output type, steady or pulsetPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse durationtDelay 0.000 - 60000.000 s 0.010 0.000 Output time delayStopAtExtremes DisabledEnabled- - Disabled Stop when min or max position is reached11.3.6 Monitored dataTable 198:SLGGIO Monitored dataName Type Values (Range) Unit DescriptionSWPOSN INTEGER - - Switch position asinteger value11.3.7 Operation principleThe logic rotating switch for function selection and LHMI presentation (SLGGIO)function has two operating inputs – UP and DOWN. When a signal is received onthe UP input, the block will activate the output next to the present activated output,in ascending order (if the present activated output is 3 – for example and oneoperates the UP input, then the output 4 will be activated). When a signal isreceived on the DOWN input, the block will activate the output next to the presentactivated output, in descending order (if the present activated output is 3 – forexample and one operates the DOWN input, then the output 2 will be activated).Depending on the output settings the output signals can be steady or pulsed. In caseof steady signals, in case of UP or DOWN operation, the previously active outputwill be deactivated. Also, depending on the settings one can have a time delaybetween the UP or DOWN activation signal positive front and the output activation.Besides the inputs visible in the application configuration in the ApplicationConfiguration tool, there are other possibilities that will allow an user to set the1MRK 502 034-UEN - Section 11Control301Technical Manual