Name Type Default DescriptionCOUNTER5 BOOLEAN 0 Input for counter 5COUNTER6 BOOLEAN 0 Input for counter 6RESET BOOLEAN 0 Reset of functionTable 310:CNTGGIO Output signalsName Type DescriptionVALUE1 INTEGER Output of counter 1VALUE2 INTEGER Output of counter 2VALUE3 INTEGER Output of counter 3VALUE4 INTEGER Output of counter 4VALUE5 INTEGER Output of counter 5VALUE6 INTEGER Output of counter 613.5.5 SettingsTable 311:CNTGGIO Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / On13.5.6 Monitored dataTable 312:CNTGGIO Monitored dataName Type Values (Range) Unit DescriptionVALUE1 INTEGER - - Output of counter 1VALUE2 INTEGER - - Output of counter 2VALUE3 INTEGER - - Output of counter 3VALUE4 INTEGER - - Output of counter 4VALUE5 INTEGER - - Output of counter 5VALUE6 INTEGER - - Output of counter 613.5.7 Operation principleEvent counter (CNTGGIO) has six counter inputs. CNTGGIO stores how manytimes each of the inputs has been activated. The counter memory for each of the sixinputs is updated, giving the total number of times the input has been activated, assoon as an input is activated. The maximum count up speed is 10 pulses persecond. The maximum counter value is 10 000. For counts above 10 000 thecounter will stop at 10 000 and no restart will take place.Section 13 1MRK 502 034-UEN -Monitoring382Technical Manual