13.15.6 Monitored dataTable 347:SSCBR Monitored dataName Type Values (Range) Unit DescriptionCBOTRVT REAL - ms Travel time of the CBduring opening operationCBCLTRVT REAL - ms Travel time of the CBduring closing operationSPRCHRT REAL - s The charging time of theCB springNO_OPR INTEGER - - Number of CB operationcycleNOOPRDAY INTEGER - - The number of days CBhas been inactiveCBLIFEL1 INTEGER - - CB Remaining life phaseL1CBLIFEL2 INTEGER - - CB Remaining life phaseL2CBLIFEL3 INTEGER - - CB Remaining life phaseL3IACCL1 REAL - - Accumulated currentspower (Iyt), phase L1IACCL2 REAL - - Accumulated currentspower (Iyt), phase L2IACCL3 REAL - - Accumulated currentspower (Iyt), phase L313.15.7 Operation principleThe circuit breaker condition monitoring function includes different metering andmonitoring subfunctions. The functions can be enabled and disabled with theOperation setting. The corresponding parameter values are “On” and “Off”. Theoperation counters are cleared when Operation is set to “Off”.The operation of the functions can be described by using a module diagram. All themodules in the diagram are explained in the next sections.1MRK 502 034-UEN - Section 13Monitoring431Technical Manual