7.15.2.4 SettingsTable 165:GOPPDOP (32) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disable / EnableOpMode1 DisabledOverPower- - OverPower Operation mode 1Power1 0.0 - 500.0 % 0.1 1.0 Power setting for stage 1 in % of calculatedpower base valueAngle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 1TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1OpMode2 DisabledOverPower- - OverPower Operation mode 2Power2 0.0 - 500.0 % 0.1 1.0 Power setting for stage 2 in % of calculatedpower base valueAngle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for stage 2TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2Table 166:GOPPDOP (32) Group settings (advanced)Name Values (Range) Unit Step Default Descriptionk 0.00 - 0.99 - 0.01 0.00 Low pass filter coefficient for powermeasurement, V and ITable 167:GOPPDOP (32) Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValuegroupsMode A, B, CAronePos SeqABBCCAABC- - Pos Seq Mode of measurement for current and voltage1MRK 506 335-UUS A Section 7Current protection281Technical manual