Table 409:B16IFCVI Output signalsName Type DescriptionOUT INTEGER Output value13.7.5 SettingsThe function does not have any parameters available in local HMI or Protection andControl IED Manager (PCM600)13.7.6 Monitored dataTable 410:B16IFCVI Monitored dataName Type Values (Range) Unit DescriptionOUT INTEGER - - Output value13.7.7 Operation principleThe Boolean 16 to integer conversion with logic node representation function(B16IFCVI) will transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, toan integer. Each INx represents a value according to the table below from 0 to 32768. Thisfollows the general formula: INx = 2x-1 where 1≤x≤16. The sum of all the values on theactivated INx will be available on the output OUT as a sum of the integer values of all theinputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) areactivated, that is = Boolean 1, it corresponds to that integer 65535 is available on theoutput OUT. The B16IFCVI function is designed for receiving the integer input from astation computer - for example, over IEC 61850. If the BLOCK input is activated, it willfreeze the logical outputs at the last value.Values of each of the different OUTx from function block B16IFCVI for 1≤x≤16.The sum of the value on each INx corresponds to the integer presented on the output OUTon the function block B16IFCVI.Name of input Type Default Description Value whenactivatedValue whendeactivatedIN1 BOOLEAN 0 Input 1 1 0IN2 BOOLEAN 0 Input 2 2 0IN3 BOOLEAN 0 Input 3 4 0IN4 BOOLEAN 0 Input 4 8 0IN5 BOOLEAN 0 Input 5 16 0Table continues on next pageSection 13 1MRK 506 335-UUS ALogic562Technical manual